Electrical Line RSS Feed In the selection of dry type transformers, how do I go about determining the proper rating of the transformer circuits?

    In the selection of dry type transformers, how do I go about determining the proper rating of the transformer circuits?

    Rating Of Transformer Circuits

    There are some subjects in the CE Code that often become a source of heated discussions by the users. Selection of dry type transformers and selection of a proper rating of the transformers circuits is one of these controversial subjects.

    So, let’s try to clarify this seemingly complex issue. First of all - we need to refresh the understanding of a circuit rating in accordance with Rule 8-104. This rule states that the rating of a circuit or a feeder is the ampere rating of the overcurrent device protecting the circuit or the ampacity of the circuit conductors, whichever is less. This rule also states that the calculated load in a circuit shall not exceed the ampere rating of the circuit (i.e. shall not exceed the rating of the circuit O/C device and the ampacity of the circuit conductors).

    This requirement of Rule 8-104 is generic through the entire Code, and of course it applies to the transformer rules in Section 26. In fact, newly adopted Rule 26-260 emphasizes a need to comply with this requirement, when a selection of the O/C protection and conductors for a transformer circuit is made. Appendix B Note on Rule 26-260 provides a clarification of correlation of the selected transformer circuit rating with the actual calculated load connected to the transformer.
    Secondly – a brief review of the unique purpose of a transformer in electrical installation is in order. Does a transformer constitute a load?

    Is it a utilization equipment? Can a connected load exceed the rating of the transformer? Let’s take a look. A transformer is an “interface” between a supply voltage and a voltage of a utilization equipment. Although a transformer is not utilization equipment, it is a load as it sustains inductive and active losses.

    As a transformer is a part of the circuit supplying a load connected to the transformer secondary, the transformer must be rated  not less than a circuit in which it operates. This means that the rating of the transformer must meet criteria of Rule 8-104(4) or (5) in respect to a continuous load connected to the transformer secondary.

    However, the fact is that the available standard ratings of typical dry type transformers are not as flexible as standard ratings of overcurrent protective devices and conductor sizes, and sometimes a transformer could be oversized for the intended connected load.

    However, Code users should be cognizant that a rating of a transformer must be selected in coordination with the connected load, and if the transformer rating is a bit large for the load, any deviation from Rule 26-256(1) for the rating of the O/C device, and any deviation from the requirements of Rule 26-258(1) and (2) for the ampacity rating of primary and secondary conductors is adequately correlated with Rule 8-104(4) or (5).

    Code users should also verify that the rating of the panelboard protected by the primary O/C device conforms with Rule 8-104(4) or (5) in addition to the provision of Rule 14-606(2).

    Let’s illustrate the above statements by an example as follows. As the building has an existing 347/600 V service and distribution system, a contractor needs to install a 75 KVA dry type transformer (primary rated current is 72 A and secondary rated current is 208 A) in order to supply a 120/208 V calculated load of 170 A in a commercial tenant unit.

    The contractor would have to undertake the following steps:

    To verify whether the calculated load is continuous in accordance with Rule 8-104(3). Note: In general, except for loads in a dwelling unit all loads are considered to be continuous, and provisions of Rule 8-104(4) or (5) must apply.(b)   

    To select the O/C device (a circuit breaker or a fused switch) on the primary of the transformer as per Rule 26-256(1). Note: This O/C device could be marked for continuous operation at 100% of the ampere rating of its overcurrent devices or for continuous operation at 80% of the ampere rating of its overcurrent devices, and such selection will impact a relationship between the continuous connected load and the rating of the O/C device in accordance with Rule 8-104(4) or (5).

    To select the ampacity of primary and secondary conductors as per Rule 26-258(1) and (2) in accordance with Tables 1 - 4, as applicable.

    To select a panelboard connected to the transformer secondary conductors. The panelboard will supply the continuous load of 170 A. Note: a panelboard supplying a connected load is an extension of the secondary conductors, and it must meet the requirement of Rule 26-258(2). In addition, the panelboard would have to be protected by the primary O/C device in accordance with Rule 14-606(2).

    Now the contractor can proceed with the selection of the components for this installation. As the connected load is considered to be continuous, a standard 80% rated circuit breaker is selected on the transformer primary. The setting of the O/C for this circuit breaker shall not exceed 125% of the transformer rated primary current. This means that the setting of the O/C can not exceed 72 A x 1.25 = 90 A. If the conductors are selected with the ampacity values based on Table 2 for this particular load, Rule 8-104(5)(a) would apply to make a correct coordination between the rating of the transformer circuit and the connected load. The contractor has two immediately obvious choices for selection of the O/C device, and these choices are: 90 A and 80 A.

    As the standard 80% rated circuit breaker is selected for the purpose of Rule 8-104(5)(a), the contractor must check whether the connected continuous load does not exceed 80% of the selected setting of the primary O/C device. The O/C device (as seen on the secondary of the transformer) cannot be smaller than 170 A x 1.25 = 212.5 A. A 90 A setting will yield 90 A x 2.88 = 259.2 A. This value will satisfy criteria of Rule 8-104(5)(a). A setting of 80 A will yield 230.4 A on the transformer secondary, and this value will also meet the criteria of Rule 8-104(5)(a) as it is larger than the minimum permitted value of 212.5 A.
    Let’s say that 80 A setting of the primary O/C is selected. Now the contractor must use Table 2 to select the ampacity of the primary conductors, as per Rule 26-258(1) not less than 90 A (No. 3 AWG is selected with the ampacity of 105 A). Respectively, the ampacity of the secondary conductors can not be smaller than 125% of the secondary rated current of the transformer (i.e. not less than 208 A x 1.25 = 260 A.). Therefore 250 MCM would be selected from Table 2 with the ampacity of 265 A. The selected primary and secondary conductors would also meet provisions of Rule 8-104(5)(a).

    The next step is the selection of the panelboard. If the contractor plans to install a standard 200 A panelboard [which will also have to meet the condition of Rule 8-104(5)(a)], this panelboard must be checked for compliance with Rule 14-606(2).

    Now it appears that the requirement of this Rule is not met, as the 80 A trip setting on the transformer primary represents 230.4 A on the secondary (which exceeds the 200 A rating of the panelboard). In order to meet the criteria of Rule 14-606(2), the primary O/C device can not exceed 200 A : 2.88 = 69.45 A. This situation leaves the contractor with the third (not very obvious choice) of selecting the setting of the primary O/C device. This choice means that a circuit breaker with a standard 70 A trip setting would adequately protect the panelboard. Although 70 A exceeds maximum allowed 69.45 A, this standard rating would be permitted under Rule 26-256(3) and under a generic relaxation allowed by Rule 8-106(1).  But would a selected 70 A setting violate Rule 26-256(1), as this selected setting is a bit smaller than the transformer rated primary current of 72 A? The answer is “No”. Provisions of Rule 8-106(1) specifically address this matter. However, it’s advisable to remember that too low a rating of the primary O/C device could result in an unintended trip of the device when the transformer is being energized, and an Appendix B Note on Rule 26-256 provides a cautionary warning to Code users in this regard. However, if the 70 A setting is, in fact selected, then the circuit breaker now would have to be rated for 100% of continuous operation, otherwise a 70 A setting on the primary will represent 202 A on the secondary, and this value would be smaller than 125% of the continuous connected load of 170 A under the condition of Rule 8-104(5)(a).

    If the contractor selects a 100% rated circuit breaker, then Rule 8-104(4)(a) would have to be used, and 202 A on the transformer secondary would satisfy requirement of this Rule.

    In fact, selection of a 70 A setting for the primary 100% rated circuit breaker would allow the contractor to use Rule 26-258(3) for reduction of the primary and secondary conductors. Now, the ampacity of primary conductors would have to be not smaller than 70 A, and No. 4 AWG primary conductors could be chosen from Table 2.

    Respectively, the secondary conductors would need to have the ampacity not smaller than 202 A, and 3/0 conductors would be permitted for use on the transformer secondary. This approach would yield significant savings to the contractor, and all applicable provisions of the CE Code would be met.

    It should be noted that if a Code user chooses to utilize a free air rated primary or secondary conductors (if a free air rating is allowed by the Code requirements), in accordance with Rule 8-104 the continuous load connected to the transformer can not exceed 85% of the rating of the transformer circuit - if the O/C device is marked for 100% of continuous operation, or can not exceed 70% of the rating of the transformer circuit - if a standard 80% rated fused switch or a circuit breaker is used as per Rule 26-256(1).

    The exercise shown in the example above could be particularly useful when a designer or installer utilizes a larger transformer (i.e. 300 KVA) and wants to install a 1000 A panelboard on the transformer secondary for the applicable connected load. A typical 300 KVA transformer would have to be protected on the 600 V primary by a 400 A O/C device, and such an O/C device would be represented on the 120/208 V secondary by 1152 A, therefore requiring installation of a 1200 A panelboard. But use of a 350 A setting (with evaluation of the precautions as recommended by the Appendix B Note on Rule 26-256) and with evaluation of all other relevant coordination aspects with Rule 8-104, would allow the installer to select a 1000 A rated panelboard. Accordingly, sizes of the primary and secondary conductors could be reduced in conformance with Rule 26-258(3).

    However, as usual, a consultation with the AHJ administering the CE Code in a specific jurisdiction is necessary before any deviation from the Code requirements on this subject is contemplated.

    Electrical Line RSS Feed Industry News

    Showing 1 - 4 of 819 Industry News.

     

    • January 30, 2012

      ABB, a leading power and automation technology group, and Thomas & Betts Corporation, a North American leader in low voltage products, announced that both companies’ boards of directors have agreed to a transaction in which ABB will acquire Thomas & Betts for $72 per share in cash or approximately $3.9 billion.

      The acquisition price represents a 24 percent premium to Thomas & Betts’ closing stock price on Jan. 27, 2012 and a 35 percent premium to the volume weighted average stock price over the past 60 trading days. The transaction is subject to approval by Thomas & Betts shareholders as well as to customary regulatory approvals, and is expected to close by the middle of 2012.

      The complementary combination of Thomas & Betts’ electrical components and AB...

    • January 30, 2012

      Siemens has entered into an agreement with RuggedCom Inc. to acquire all of the issued and outstanding common shares of RuggedCom by way of a friendly, board-supported takeover bid. The Canadian company listed on the Toronto Stock Exchange is a leading provider of communications and networking solutions for harsh industrial environments. The takeover bid is for C$33.00 per common share in cash, or a total transaction value of approximately C$382 million. RuggedCom's Board of Directors has unanimously determined to support, and to recommend that RuggedCom's shareholders accept the offer. Subject to the satisfaction or waiver of certain limited conditions, Siemens expects to take up shares under the offer in the second half of March 2012.

      With annual revenues of approximately US$94...

    • January 27, 2012

      Ballard Power Systems has announced signing of a non-binding Memorandum of Understanding (MOU) with Tata Motors (India) for 12 FCvelocity™-1100 fuel cell stacks. These stacks are expected to power zero-emission buses planned for demonstration in various Indian cities. Delivery to Tata Motors is planned for 2012 and 2013, in-line with that Company's plans.

      Tata Motors, one of the world's largest bus OEM's, displayed the first fuel cell bus built in India at "Auto Expo 2012" held in New Delhi January 6-11, 2012. The bus is powered with a Ballard FCvelocity™-1100 fuel cell stack, previously delivered to Tata Motors in 2011.

      Mr. P.M. Telang, Managing Director (India Operations) at Tata Motors said, "We strive to be leaders in the use of technology, while main...

    • January 26, 2012

      The MEET (Mechanical Electrical Electronic Technology) Show is set to open in Moncton, May 2-3. This biennial event attracts exhibitors from all over Canada and the US, displaying the very latest equipment available to the mechanical and electrical industries.

      MEET has proven itself to be one of the top industry events in Canada. Acting as a comprehensive marketplace, this show gives industry professionals the unique opportunity to see mechanical and electrical companies from across North America under one roof.

      MEET is the second largest event for industry in Canada and the largest trade event east of Montreal. The economic impact for Moncton is significant given that the majority of exhibitors come from outside the local area. The last edition of MEET in 2010 welcome...

    Electrical Line RSS Feed Keeping Current

    Showing 1 - 4 of 299 Keeping Current.

     

    • February 1, 2012

      GE ENERGY INDUSTRIAL SOLUTIONS announces the appointment of Adrian Thomas as the new Regional Sales Leader responsible for driving sales of electrification products across Canada. Dale Wilson, Global Sales Leader for GE Energy’s Industrial Solutions business says the company has a dedicated sales organization of 60 experienced professionals and Adrian will bring strong...

    • January 31, 2012

      LIND EQUIPMENT announces the appointment of ElectriXwest Agencies Ltd. as its electrical sales agent in Alberta. ElectriXwest Agencies will continue to build Lind Equipment’s presence in Alberta and serve electrical distributors’ demands for high quality, fairly priced portable electrical equipment for the toughest workplaces. With a combination of outside sales to demonstrate Lind’s products to end-users and distributors, and a strong background in technical specification to work with engineers, ElectriXwest is well poised to help Alberta to work confidently with Lind Equipment’s products. Brian Astl, VP Sales for Lind Equipment said the well-trained, attentive sales representatives in Edmonton and Calgary makes for an excellent platform from which to...

    • January 25, 2012

      IDEAL INDUSTRIES NETWORKS, the networking division of IDEAL Industries, Inc., one of the world's largest manufacturers of LAN Test and Measurement products that improve the quality and lower the cost of data communication, has appointed Mark Barmettler as its new Director of Engineering in the US. Barmettler brings over a quarter century of engineering and...

    • January 23, 2012

      SOMMERS MOTOR GENERATOR SALES LTD. announces its expansion to a new Atlantic Canada headquarters at 707 Malenfant Blvd. Dieppe, New Brunwick. Sommers designs and builds customized standby, PTO and off-grid generator power solutions and is the leading Canadian manufacturer of packaged generator systems for residential, commercial and industrial applications. It maintains the country’s largest privately held inventory of generators for sale or rent from 3 kW to 2 MW. Established in Tavistock, Ontario, in 1936, Sommers has been a trusted name in generating, delivering and applying electrical power for three generations.

      Chris McGregor, Sommers General Manager and Vice President Sales & Business Development, explains that, “We chose Dieppe as...

    Electrical Line RSS Feed Upcoming Events

    • 1

    Electrical Line RSS Feed Career Opportunities

     
    • 1

    Electrical Line RSS Feed Product Safety Alert!

    View the latest safety alerts on recalled and counterfeit products:

     

    Electrical Line RSS Feed EL Newswire

    Electricalline Newswire
    Keep up-to-date with the latest news affecting your industry, personnel appointments, career opportunities, upcoming events and new product launches by subscribing to EL Newswire.
    Email:

    Electrical Line RSS Feed Ask the Expert

    Having trouble finding answers? Let our industry experts provide answers to your questions. Submit your question here.

    Below are answers to some recently asked questions:

     

    Electrical Line RSS Feed Product Showcase

    Showing 1 - 3 of 503 results.
    • January 30, 2012

      Ideal for various process and water related industries, Hammond Manufacturing’s HN4_SS series of stainless steel two door cabinets are robust units that can be mounted on walls or equipment. Designed to house electrical, electronic, hydraulic or pneumatic controls and instruments installed in harsh or aggressive industrial environments, the HN4_SS range is available as standard in 12 different sizes ranging...

      read more
    • January 27, 2012

      A new high-speed data-capture option has been introduced for the Yokogawa WT1800 precision power analyzer.

      The new /HS option provides fast, accurate measurements of power parameters such as voltage, current, power, torque, speed and mechanical power with millisecond response. This allows it to capture numeric data on the change of status during one rotation of a motor when the motor is started,...

      read more
    • January 26, 2012

      WattStopper has introduced the rugged FSP-211 Digital High/Low Passive Infrared Fixture Integrated Outdoor Sensor to conveniently control lighting in areas such as parking facilities, gas stations, pedestrian pathways and warehouses. The sensor, which was accepted into the prestigious 2011 IES Progress Report, mounts in a lighting fixture and provides motion-based multi-level control combined with...

      read more


    Browse Virtual Issues

    * mouse over magazine cover for issue identification


    Electrical Line RSS Feed Google Adsense